AWG to mm² conversion and wire size chart

Convert AWG wire gauge to mm² and diameter, resistance per km, the nearest standard metric cross-section, and reverse lookup from mm². With a full AWG chart.

Cross-section
–mm²
Diameter
–mm
Resistance, copper (20 °C)
–Ω/km
Resistance, aluminium (20 °C)
–Ω/km
Next larger standard mm²
–mm²
AWG needed for the given mm²
–AWG

How it works

AWG (American Wire Gauge) is the North American wire size standard: the higher the number, the thinner the wire, and every 3 steps roughly halve the cross-section. 0000 (4/0) is the thickest, 40 a very fine wire.

Formula

d = 0.127 mm × 92^((36 − n) / 39)
A = π/4 × d²
R = ρ / A   (ρCu = 0.01724, ρAl = 0.02826 Ω·mm²/m)

The IEC 60228 metric series does not match AWG, so when substituting always choose the larger cross-section. Resistance applies to solid conductors at 20 °C; stranded wire is slightly higher. Current capacity depends on installation and insulation and must be taken from the relevant standard.

Chart

AWGDiameter mmmm²Ω/km (copper)
000011.684107.2190.16
00010.40585.0290.20
009.26667.4310.26
08.25253.4750.32
17.34842.4080.41
26.54433.6310.51
35.82726.6710.65
45.18921.1510.82
54.62116.7731.03
64.11513.3021.30
73.66510.5491.63
83.2648.3662.06
92.9066.6342.60
102.5885.2613.28
112.3054.1724.13
122.0533.3095.21
131.8282.6246.57
141.6282.0818.29
151.4501.65010.45
161.2911.30913.17
171.1491.03816.61
181.0240.82320.95
190.9120.65326.41
200.8120.51833.31
210.7230.41042.00
220.6440.32652.97
230.5730.25866.77
240.5110.20584.23
250.4550.162106.16
260.4050.129133.86
270.3610.102168.86
280.3210.081212.85
290.2860.064268.55
300.2550.051338.72
310.2270.040426.76
320.2020.032538.78
330.1800.025678.78
340.1600.020857.76
350.1430.0161,077.56
360.1270.0131,357.56
370.1130.0101,724.10
380.1010.0082,155.12
390.0900.0062,736.67
400.0800.0053,448.20