Voltage drop and cable size calculator

Calculate voltage drop for single- and three-phase cables with copper or aluminium conductors, power loss and the minimum cross-section for a permitted drop.

Voltage drop
–V
Voltage drop in percent
–%
Voltage at load
–V
Power loss
–W
Minimum cross-section
–mm²
Suggested standard size
–mm²

How it works

Voltage drop arises across the resistance of the conductors. In a single-phase circuit the current flows out and back, so twice the length is used; in a balanced three-phase system the factor is √3, relative to the line-to-line voltage.

Formula

1~: ΔU = 2 · L · I · ρ · cos φ / A
3~: ΔU = √3 · L · I · ρ · cos φ / A
ρ(T) = ρ20 · (1 + α · (T − 20))

The calculation neglects cable reactance, which is a good approximation below about 25–35 mm². At operating temperature resistance is higher: about 20% more for copper at 70 °C. The cross-section must also be checked for current capacity and protection.